1.4.3 Transport of the Components
Ambient and operating conditions-Transport
Description Symbol Unit Value
Temperature range
T
a_tran
℃ -25…70
Relative humidity – % 5…95
Absolute humidity –
g/m
3
1…60
Climate category (IEC 721) – – 2K3
Moisture condensation – – not allowed
Icing – – not allowed
Tab. 1-2: Transport conditions
1.4.4 Storage of the Components
Damage to the components caused by long
storage periods!
Some components contain electrolytic capacitors which may deteriorate dur‐
ing storage.
When storing these components for a long period of time, operate them once
a year for at least 1 hour with power on:
● Fv with mains voltage U
LN
● FELB with DC bus voltage U
DC
Ambient and operating conditions-Storage
Description Symbol Unit Value
Temperature range
T
a_store
℃
-25…55
Relative humidity – % 5…95
Absolute humidity –
g/m
3
1…29
Climate category (IEC 721) – – 1K3
Moisture condensation – – not allowed
Icing – – not allowed
Tab. 1-3: Storage conditions
DOK-RCON02-FV*********-IB08-EN-P Bosch Rexroth AG 19/259