6.2 Commission Process
6.2.1 Check and Preparation before Commissioning
1. Check if the wiring is correct. Particularly, ensure that the output termi‐
nals U, V and W of the frequency converter are not connected to the
power supply and that the ground terminal is well grounded.
2. Ensure that there are no short circuits between terminals, live terminals
or short circuit to ground.
3. Ensure that terminal connections, connectors and screws are secure.
4. Ensure the motor is not connected to other loads.
5. Check that all inputs are off before powering on, to ensure that the fre‐
quency converter will be started as expected and no unexpected action
occurs.
6. Make the following checks after powering on:
● The set frequency flashes on the display (without fault indication); if
"software doesn't match" is displayed, it indicates the software ver‐
sion of operating panel and control board doesn't match, for which
you need to consult the service.
● The displayed parameters match with the field application.
Bosch Rexroth AG DOK-RCON02-FV*********-IB08-EN-P66/259
Rexroth Frequency Converter Fv
Commissioning