Installation of Motor Power Cable
● Use shield motor power cable or run motor power cables in a shielded
duct.
● Use the shortest possible motor power cable.
● Ground shield of motor power cable at both ends over the largest possi‐
ble surface area to establish a good electrical connection.
● It is recommended to run motor lines in shielded form inside the control
cabinet.
● Do not use any steel-shielded lines.
● The shield of the motor power cable must not be interrupted by mounted
components, such as output chokes, sine filter or motor filters.