SET.28
of 68
SEL-787 Settings Sheets
Global Settings (SET G Command)
SEL-787 Relay Instruction Manual Date Code 20081022
Date _______________
Group______________
Phasor Measurement (PMU)
EN SYNCHRO PHSOR (Y, N) (All subsequent PMU settings
hidden if EPMU :=N)
EPMU :=
MESSAGES PER SEC (1, 2, 5, 10)
MRATE :=
STATION NAME (16 characters)
PMSTN :=
PMU HARDWARE ID (1–65534)
PMID :=
VOLTAGE DATA SET (V1, ALL, NA)
(Hidden if no voltages) PHDATAV :=
VOLT COMP ANGLE (-179.99 to 180.00 deg)
(Hidden if
PHDATAV := NA)
VCOMP :=
CURRENT DATA SET (I1, ALL, NA)
PHDATAI :=
CURRENT SOURCE (IW1, IW2, BOTH)
(Hidden if
PHDATAI := NA)
PHCURR :=
IW1 COMP ANGLE (-179.99 to 180.00 deg)
(Hidden if PHCURR := IW2 or if PHDATAI := NA)
IW1COMP :=
IW2 COMP ANGLE (-179.99 to 180.00 deg)
(Hidden if PHCURR := IW1 or if PHDATAI := NA)
IW2COMP :=
NUM ANALOGS (0–4)
NUMANA :=
NUM 16BIT DIGTAL (0, 1)
NUMDSW :=
TRIG REASON BIT1 (SEL
OGIC) TREA1 :=
TRIG REASON BIT2 (SEL
OGIC) TREA2 :=
TRIG REASON BIT3 (SEL
OGIC) TREA3 :=
TRIG REASON BIT4 (SEL
OGIC) TREA4 :=
TRIGGER ((SEL
OGIC) PMTRIG :=
CTRL BITS DEFN (NONE, C37.118)
IRIGC :=
Breaker Failure
52A INTERLOCK (Y, N) 52ABF :=
BRKR1 FAIL DELAY (0.00–2.00 sec)
BFD1 :=
BRKR1 FAIL INITIATE ((SEL
OGIC) BFI1 :=
BRKR2 FAIL DELAY (0.00–2.00 sec)
BFD2 :=
BRKR2 FAIL INITIATE ((SEL
OGIC) BFI2 :=
Through Fault
THR FLT WDG (OFF, 1, 2) THFLTD :=
ENABLE THR FLT ((SEL
OGIC)
(Hidden if THFLTD := OFF)
ETHRFLT :=
THR FLT ALARM PU (50.0–900.0 %)
(Hidden if THFLTD := OFF)
THFLTPU :=
XFMR IMPEDANCE (2.0–40.0 %)
(Hidden if THFLTD := OFF)
XFMRZ :=