F.30
SEL-787 Relay Instruction Manual Date Code 20081022
IEC 61850 Communications
ACSI Conformance Statements
Transmission of Sample Value Model (SVC) (Clause 16)
Multicast SVC
S45 SendMSVMessage
MC c10
g
c10
g
S46 GetMSVCBValues
TP O
b
O
b
S47 SetMSVCBValues
TP O
b
O
b
Unicast SVC
S48 SendUSVMessage
MC c10
g
c10
g
S49 GetUSVCBValues
TP O
b
O
b
S50 SetUSVCBValues
TP O
b
O
b
Control (Clause 16.4.8)
S51 Select
M
a
O
b
YES
S52 SelectWithValue
TP Ma O
b
YES
S53 Cancel
TP O
b
M
a
YES
S54 Operate
TP M
a
M
a
YES
S55 Command-Termination
TP M
a
M
a
YES
S56 TimeActivated-Operate
TP O
b
O
b
File Transfer (Clause 20)
S57 GetFile
TP O
b
M
a
S58 SetFile
TP O
b
O
b
S59 DeleteFile
TP O
b
O
b
S60 GetFileAttributeValues
TP O
b
M
a
Time (Clause 5.5)
T1 Time resolution of internal
clock (nearest negative
power of 2 in seconds)
2-10 (1 ms) T1
T2 Time accuracy of internal
clock
10/9
T1
YES
T2
YES
T3
YES
T4
YES
T3 Supported TimeStamp
resolution (nearest negative
power of 2 in seconds)
2-10 (1 ms) 10
a
M = Mandatory.
b
O=Optional.
c
c6 shall declare support for at least one (BRCB or URCB).
d
c7 shall declare support for at least one (QueryLogByTime or QueryLogAfter).
e
c8 shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage).
f
c9 shall declare support if TP association is available.
g
c10 shall declare support for at least one (SendMSVMessage or SendUSVMessage).
Table F.29 ACSI Services Conformance Statement (Sheet 3 of 3)