132 FLOWSIC100 · Operating Instructions · 8012513/YSA5/V2-1/2016-07 · © SICK Engineering GmbH
Start-up and Parameter Settings
Subject to change without notice
Parameters
Parameter 1
Source value Velocity of gas The selected measured variable is output on the analog output.
Sound velocity
Q act.
Q std.
Range low Lower measuring
range limit
Physical value at live zero
Range high Upper measuring
range limit
Physical value at 20 mA
Live zero Zero point (0, 2 or 4
mA)
Select 2 or 4 mA to differentiate clearly between measured value and
device switched off, or current loop interrupted.
Limiting value Measured
value
Velocity of gas Selection of measured variable for monitoring a set limit value
Sound velocity
Q act.
Q std.
Direction
Switch at If a value 0 is set, the limit value relay switches when the value for the
selected measured variable is exceeded.
Optional digital output module configuration without function at present
Field Parameters Remark