Chapter 12 Operating instructions
S300
122 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8010948/YY96/2016-02-17
Subject to change without notice
Technical specifications
Minimum Typical Maximum
Functional data
Resolution of the S300 Medium Range 30, 40, 50, 70 mm
Protective field of the S300 Medium Range
At 30 mm resolution 1.25 m
At 40 mm resolution 1.60 m
At 50 mm resolution 2.00 m
At 70 mm resolution 2.00 m
Resolution of the S300 Long Range 30, 40, 50, 70, 150 mm
Protective field of the S300 Long Range
at 30 mm resolution 1.25 m
at 40 mm resolution 1.60 m
at 50 mm resolution 2.10 m
at 70 mm resolution 3.00 m
at 150 mm resolution 3.00 m
Scan angle 270°
Remission 1.8% Several
1000% (re-
flectors
23)
)
Angular resolution 0.5°
Protective field supplement generally
necessary
100 mm
Supplement for retroreflectors in scan plane
at a distance of less than 1 m to the protective
field boundary
200 mm
Measurement error on data output via RS<422
(S300 Medium Range up to 2 m in the
specified remission range)
Systematic error ±20 mm
Statistical incl. systematic errors
at 1 ±28 mm
at 2 ±36 mm
at 3 ±44 mm
at 4 ±52 mm
at 5 ±60 mm
23)
Complies with Diamond Grade 3000X™ (approx. 1250 cd/lx × m²).