Chapter 7 Operating instructions
S3000
116 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8009942/WK81/2012-11-28
Subject to change without notice
Application examples and
connection diagrams
7.5.8 Protective field switching between an S3000 and an S300 with static and
dynamic inputs
S3000 Professional with S300 Professional in an EFI system with relays/contactors;
Operating mode: without restart interlock with external device monitoring; direction of
travel-dependent dynamic protective field switching using the incremental encoders C and
D as well as static protective field switching using the control inputs A and B of the S3000.
The protective fields affect the OSSDs on the host.
S3000 Expert with S300 Mini Remote in an EFI system with relays/contactors; Operating
mode: without restart interlock with external device monitoring; direction of travel-
dependent dynamic protective field switching using the incremental encoders C and D as
well as static protective field switching using the control inputs A and B of the S3000. The
protective fields affect the OSSDs on the host.
Fig.
84
:
Connection diagram
for protective field switching
between an S3000 and an
S300 using static and
dynamic inputs
Fig.
85
:
Connection diagram
for protective field switching
between an S3000 and an
S300 Mini using static and
dynamic inputs
S3000
Professional
S300
Professional
S3000
Expert
S300 Mini Remote