Diagnostics
11.4 Error and status indications on the 7@segment display
T
his section explains the meaning of the error and status indications of the 7<segment
display and how you can respond. You will find a description of the positions and symbols
on the S3000 in section 3.4 “Status indicators” on page 27.
T
he lock-out operational status
I
n case of certain faults or an erroneous configuration, the device can go into the lock-out
operational status. To place the device back in operation, proceed as follows:
Rectify the cause of the fault as per Tab. 39.
Switch off the power supply for the S3000, wait at least 3 seconds and then switch back
on the power supply.
Or:
Restart the safety laser scanner with the aid of the CDS.
Display Possible cause Rectification of the error
, , , ,
, , ,
Power-up cycle — all
segments are
activated sequentially.
No error
Indication of protective field and contour infringements in the dual field mode
Object in protective
field
or
Surrounding contour
changed
27)
Object in the
simultaneous
protective field
or
Surrounding contour
27)
changed
No error. The status indication eases system
testing on the use of simultaneous protective
fields or in an EFI system (if the OSSDs on the
guest are not used, a protective field
infringement is not signaled via the red LED as
required in the standard).
Indication of protective field and contour infringements in the dual protective field mode
Object in the first
protective field of the
field set
or
Surrounding contour
27)
changed
No error
Object in the second
protective field of the
field set
or
Surrounding contour
27)
changed
No error
27)
If the contour as reference function is configured.
indications on the 7>segment
display