Commissioning
Step Display Meaning
Other display Safety lock activated. Malfunction in external
conditions or in the device itself (see section 11.4
“Error and status indications on the 7<segment
display” on page 135)
I
f the system plug has also been replaced, then the configuration must be transferred to
the S3000 with the aid of the CDS. In this case acceptance by qualified safety personnel is
necessary (see section 9.1 on page 120).
In an EFI system with two safety laser scanners, set the address of one of the scanners
to guest!
If the system plug has also been replaced, then re-fit the jumper between the connection
terminals 7 (ERR) and 10 (A1) on a guest device (see section 6.1 “System connection” on
page 96).
The jumper always defines the guest device. This jumper is never allowed to be fitted on
the host device.
Display
Meaning
The device is operational, object in
protective field and warning field.
The device is operational, object in
warning field.
The device is operational, no object in
protective field and warning field.
The device is operational, no object in
protective field and warning field.
Control switch for restart interlock or
reset must be operated.
Other display Safety lock activated. Malfunction in
external conditions or in the device
itself (see section 11.3 “Error and
status indications on the LEDs” on
page 133)
Note
WARNING
the power up sequence