Addr. Parameter Setting Options Default Setting Comments
7253 bef.3.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 3. Cycle: 50N-3
7254 bef.4.Cy:50-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50-3
7255 bef.4.Cy:50N-3 Set value T=T
instant. T=0
blocked T=∞
Set value T=T before 4. Cycle: 50N-3
7260 51 IEC 2.C Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse 51 IEC Curve before 2.cycle
7265 51N Recl. 2.C Curve A (101)
Curve B (117)
Curve C (133)
Curve D (116)
Curve E (132)
Curve K (162)
Curve N (104)
Curve R (105)
Curve W (138)
Curve 2 (135)
Curve 3 (140)
Curve 8 (113)
Curve 8* (111)
Curve 9 (131)
Curve 11 (141)
Curve A (101) 51N Recloser Curve before 2.cycle
7266 67-TOC IEC 2.C Normal Inverse
Very Inverse
Extremely Inv.
Long Inverse
Normal Inverse 67-TOC IEC Curve before 2.cycle
7267 67-TOC ANSI 2.C Very Inverse
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Extremely Inv.
Definite Inv.
Very Inverse 67-TOC ANSI Curve before 2.cycle
Functions
2.14 Automatic Reclosing System 79
290 SIPROTEC Compact, 7SC80, Manual
E50417-G1140-C486-A8, Edition 07.2017