Mounting and installation of the compact control panels
5
104 | 354
5.7.3.3 X11 monitoring signals
Pin Designation Description
9 NC Not used
8 NC Not used
7 SA Control line for even current distribution (only when switching in parallel)
6 SA Control line for even current distribution (only when switching in parallel)
5 F Connection for temperature sensor (master only)
4 F Connection for temperature sensor (master only)
3 BS Signaling: Battery fault (↑ normal operation 1/3 closed)
2 NS Signaling: Mains fault (normal operation 1/2 closed)
1 S Signaling: Common fault contact
Admissible cable cross-section: 0.2…2.5 mm²
Figure 46: Wiring of the single power supply SV 24V-150W-A4
1 Cable tree to periphery board or fire terminal board
See also
2 X1 supply [➙ 75]
2 X1 supply [➙ 82]
2 X1 supply [➙ 90]