nting and installation FC2080
Installing an Ethernet switch (modular) FN2012
6
325 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
1 Lateral support rail in the 19" pedestal housing
2 Mounting holes in lateral support rail
3 Large mounting bracket from FHA2029
4 4x mounting holes in mounting bracket
5 4x fixing screws for mounting bracket
6 U-rail installed
7 Retaining bracket installed
1. Mount the large mounting bracket (3) in the position shown and screw the four
screws (5) into the threaded holes (2) in the lateral support rail.
2. Wire up the Ethernet switch according to chapter 'Wiring [ 154]'.
6.17.2 FN2012 in station with housing (19", pedestal housing)
Figure 183: FN2012 in the 19" pedestal housing of the FC2080
1 Side wall of 19" pedestal housing
2 Large mounting bracket from mounting kit FHA2029
3 DIN rail with retaining bracket
4 FN2012
w The DIN rail clip is mounted on the FN2012.
1. Holding it at an angle and working from below, place the FN2012 (4) against
the bottom edge of the DIN rail (3) and press it up so that the retaining clamp in
the flange gives way.
2. Push the upper flange into position over the DIN rail and release the spring
pressure.
a The DIN rail clip is now in place.
3. Check that the DIN rail clip is fully engaged on the DIN rail.
4. Wire up the FN2012 according to chapter 'Wiring [ 154]'.
See also
2 Wiring [ 154]