Building Technologies
6.13 Installing the operating unit and operating add-on
The fire control panel FC2080 has no integrated operating unit. The operating unit
and a maximum of two operating add-ons form a station of their own within the
FC2080. The communication takes place via FCnet. The current load of the
optional operating unit must be incorporated into the current balance of the
FC2080.
NOTICE
Communication error
● If an operating unit is installed in the FC2080, then the operating unit must be
equipped with a network module (SAFEDLINK) FN2001-A1 with a product
NOTICE
If one or more operating units, within or outside the stations, are connected to the
same power supply as the FC2080 or FG2020, ground fault monitoring must be
deactivated on the operating units by setting switch 'S38' to the 'OFF' position.
Otherwise, ground fault monitoring will always be active.
6.13.1 Installation
Before an operating terminal is installed, the following components must first be
mounted on the operating unit.
● Network module (SAFEDLINK) FN2001-A1 with ES ≥ 12, for connecting to the
FC2080
● Adapter and connection cable for the power supply
– Supplied with processor unit (19", FC2080) FCC2002-A1
Preparing the operating unit
The network module (SAFEDLINK) FN2001-A1 must be installed on connector
X13 of the operating unit (main module slot).