Mounting and installation of the compact control panels
Redux
module [DE]
5
195 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
1. Using a knife, cut out the cover foil along the opening for the key switch (1)
(working from the front if possible).
2. Place the cylinder of the key switch (2) on the spacer bolts (4) and screw it
tightly in place using the two screws (3).
3. From the front, press the guard ring for the key switch onto the lock cylinder (2)
until it snaps into place, as shown in the figure above.
5.23 Redux module [DE]
5.23.1 Installation
The Redux module RGQ:FAT-Redux-FS20 is an option for redundantly activating
the fire brigade indication panel (FAT) [DE]. It is fitted on the DIN rail in the fire
control panel.
Figure 105: Installation position of the Redux module
1 DIN rail
2 Redux module
X1 Connection terminal for line 1 and 2 to the FAT / VAREX
X2 Connection terminal for signals to the fire control panel
X3 Input for system voltage
X4 Output for power supply of the FAT
X5 Connection terminal fault relay
1. Place the Redux module (2) on the DIN rail (1) with the clamp.
2. Connect the Redux module according to the pin assignment.
X1
X4
X3
X5
X2
1
2