5.15.3 Pin assignments
5.15.3.1 Power A and B sockets, fault contact
The 5-pin connector for the power supply is supplied with the fiber optic cable
network module.
Pin Designation Description
1 DC+ 9…30 V Supply input +
2 DC- 9…30 V Supply input -
3 COM Fault relay: Common contact
4 NO Fault relay: Normally open
5 NC Fault relay: Normally closed
Admissible cable cross-section: 0.14…1.5 m
The power supply need not be monitored and made redundant when installing
in the fire control panel.
The supply line must be shielded with remote network module.
Relay contact opens in the event of an error. The display indicates the error
(COM and NC are connected).
Figure 65: Connector for Power A and Power B sockets
1
2
3
4
5
+
-
C
NO
NC
5
4
3
2
1