Mounting and installation of the compact control panels
Input/output module FDCIO224 [DE]
5
197 |
Building Technologies
5.24 Input/output module FDCIO224 [DE]
5.24.1 Installation
The input/output module FDCIO224 has four potential-free contact inputs and four
control outputs for VdS-compliant connection of the VdS extinguishing interface.
For this application it must be installed in the fire control panel. The input/output
module is mounted onto the DIN rail.
Figure 106: Installing the input/output module FDCIO224 in the fire control panel
1 Input/output module FDCIO224
2 DIN rail
3 Mounting feet
1. Insert the two mounting feet (3) at the sides of the input/output module.
2. Push the input/output module (1) with the mounting feet (3) against the DIN rail
(2) until the mounting feet snap into place.
3. Connect the input/output module according to the pin assignment. You will find
the pin assignment in document 007023, Technical Manual.
2
1