EasyManua.ls Logo

Siemens FS20 - Connection Module (Card Cage); Installation

Siemens FS20
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and installation of the compact control panels
Connection module (card cage)
5
158 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.17 Connection module (card cage)
5.17.1 Installation
This component is installed in exactly the same way
as for the operating units
with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027.
The connection module (card cage) FCA2006-A1 is always needed in conjunction
with the card cage (2 slots) or card cage (5 slots). It is fitted in the corresponding
fire control panels the factory and only has to be replaced in the event of a repair.
Figure 83: Installation of connection module (card cage)
1 Spacers (2 pieces)
2 Connection module (card cage)
3 Operating unit
4 Fixing screws (2 pieces)
X11 Connector for connection module (card cage)
X500 Module bus cable connection
1. Attach the connection module (card cage) (2) to the connector intended for it
(X11) on the operating unit (3) as shown.
2. Fasten the module to the spacers (1) using the two screws (4).
3. Connect the flat cable for the module bus of X500 connection module with
X501 on card cage.
3
4
1
2
X11
X500

Table of Contents

Other manuals for Siemens FS20

Related product manuals