Mounting and installation of the compact control panels
Ethernet switch FN2008 and safety module FN2009
5
258 | 354
5.37.6 Modifications to the modules for class B
For the 'Ethernet switch (MM)' and 'Security module (firewall)' modules, the
following modifications are required to the wiring to reduce fault transmission from
limit value class A to class B:
● For each electrical Ethernet connection, one ferrite core, type Würth Elektronik,
742 701 51
● For each supply connection, one ferrite core, type Würth Elektronik, 742 715 4
Figure 138: Modifications to the wiring for class B