Mounting and installation of the compact control panels
5
226 | 354
5.34.1 Adjustment elements
The EVAC-NL indicator is configured with the switch S20.
Setting for one or the first EVAC-NL
Switch S20 Meaning
1 2 3 4 5 6
S0 S1 S2 Master Syn (Empty)
ON OFF Device address 1
1
ON ON OFF Device address 2
ON ON OFF Device address 3
ON ON ON OFF Device address 4
ON ON OFF Device address 5
X X X ON ON
Mimic display outputs are actuated
and polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position according to addresses 1 to 5
1
If working with a single EVAC-NL indicator (10 zones) and if working with the first
EVAC-NL indicator, S20/4 (Master) must always be set to ON. If used in the EVAC-
NL mimic display driver, the S20/5 (Syn) switch must also be ON.
Each address can be assigned only once per
The factory setting is always made for the application in question.