Mounting and installation of the compact control panels
Operating add
-
on with 20 zones EVAC
-
NL [NL]
5
227 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
Setting for the second and/or any subsequent EVAC-NL indicator
Switch S20 Meaning
1 2 3 4 5 6
S0 S1 S2 Master Syn (Empty)
OFF OFF Device address 1
ON OFF OFF Device address 2
1
ON OFF OFF Device address 3
ON ON OFF OFF Device address 4
ON OFF OFF Device address 5
X X X OFF ON
Mimic display outputs are actuated
and polled (LED, keys and key switch)
Blank fields = Switch in 'OFF' position
X = Switch position according to addresses 1 to 5
1
2 EVAC-NL indicators must not be operated on the same address (per station).
On the second or any subsequent indicator, the address must always be set 1
higher (slave). If used in the EVAC-NL mimic display driver, the S20/5 (Syn) switch
must also be ON.
Each address can be assigned only once per station.
The factory setting is always made for the application in question.