Mounting and installation of fire terminal (Touch)
Inst
allation in 19" pedestal housing of the FC2080
7
331 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
7.2 Installation in 19" pedestal housing of the FC2080
The installation instructions described below apply to all operating units.
Before an operating terminal is installed, the following components must first be
mounted on the operating unit.
Network module (SAFEDLINK) FN2001-A1 with ES 12, for connecting to the
FC2080
Adapter and connection cable for the power supply
Supplied with processor unit (19", FC2080) FCC2002-A1
Preparing the operating unit
The network module (SAFEDLINK) FN2001-A1 must be installed on connector
X13 of the operating unit (main module slot).
Figure 188: Installing the required components, taking operating unit FCM2028-A1 as an example
1 Operating unit
2 Flange with threaded holes for securing the module
3 Connector strip X13 for network module
4 Network module (SAFEDLINK) FN2001-A1 with ES 12
1
2
3
4
5
6
7
8