Mounting and installation FC2080
Processor unit (19", FC2080)
6
268 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
6.2.3 Pin assignments
6.2.3.1 X11/X12 connection terminals for SDL1/SDL2
The FCnet is connected to the following connection terminals:
X11 'SDL1'. FCnet connection for network module (SAFEDLINK, CC) of the
CPU card (FC2080)
X12 'SDL2' FCnet connection for network module (SAFEDLINK, CC) of the
communication card (FC2080) or the redundant CPU card (FC2080)
X3 FCnet connection for network module (SAFEDLINK) on connector X13
(main module) on the optional operating unit
Pin Designation Description
4 A1 Line 1 (+)
3 B1 Line 1 (–)
2 A2 Line 2 (+)
1 B2 Line 2 (–)
Admissible cable cross-section: 0.2…2.5 mm²
The FCnet networking of the FC2080 or the FG2020 is always connected via two
network modules irrespective of the number of CPU cards. The network module
on the communication card is used with a CPU card.
Figure 143: FCnet networking of FG2020 without operating unit
B2A2B1A1B2A2B1A1
1234 1234
X11
X12
FCC2003
FC2080
FCnet
FCnet