ation of the compact control panels
Mounting and assembling a station
5
64 | 354
5.2.3 Connect the mains cable
5.2.3.1 Cable routing
Guidelines
● The network cables must be inserted from above.
● The mains lead must be placed along the left side of the housing (observe
EMC zone boundary).
● Signal and control lines must only be fed into the housing on the right from
above or from the rear.
● Batteries must be installed so that they cannot leak.
● No cable openings should be made in the base of the housing, unless an
additional housing is mounted below the station to accommodate the batteries.
Figure 27: Laying the mains cable for the Standard housing (left) and the Comfort housing (right)
1 EMC-critical zone (no high-voltage power permitted)
2 Mains connection from below (not recommended)
3 Disconnect terminal blocks
4 Cable strain relief for mains supply line
5 Mains connection from above (recommended)
6 EMC boundary
2
3
5 6
1
4
2
3
4