Mounting and install
ation of the compact control panels
Mounting and assembling a station
5
64 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.2.3 Connect the mains cable
5.2.3.1 Cable routing
Guidelines
The network cables must be inserted from above.
The mains lead must be placed along the left side of the housing (observe
EMC zone boundary).
Signal and control lines must only be fed into the housing on the right from
above or from the rear.
Batteries must be installed so that they cannot leak.
No cable openings should be made in the base of the housing, unless an
additional housing is mounted below the station to accommodate the batteries.
Figure 27: Laying the mains cable for the Standard housing (left) and the Comfort housing (right)
1 EMC-critical zone (no high-voltage power permitted)
2 Mains connection from below (not recommended)
3 Disconnect terminal blocks
4 Cable strain relief for mains supply line
5 Mains connection from above (recommended)
6 EMC boundary