Mounting and installation of the compact control panels
Mounting and assembling a station
5
63 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
Mounting steps
WARNING
Heat bridge between the station and mounting surface caused e.g.
by
overheating of the batteries
Danger of fire
If you mount the station on a flammable wall, all cut-out sections for the
mounting holes must be sealed usin
g the supplied aluminium stickers.
1. Break out the required cable entries at the bottom of the rear panel and the
cover of the additional housing (4, 5), as well as the mounting holes for housing
assembly (3).
2. Attach edge protection strips or rubber grommets to the cable entries.
3. Fasten the rear panel of the additional housing (1) in the same way as that of
the station. Make sure that the alignment is exact.
4. Stick the supplied aluminium stickers over all holes for wall mounting.
5. Attach the two housings to one another by putting screws through the mounting
holes (3) in the bottom and the cover.
NOTICE
Battery leakage
Damage to hardware
If you assemble two housings one on top of the other, you fit the batteries in
the lower housing.