Mounting and installation of the compact control panels
Periphery board (4 loops)
5
82 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
w Components that make access to the periphery board difficult are removed
(e.g. mounting plate).
w Connections and plug-in contacts are disconnected and the cables are
labelled.
w The periphery board is removed.
1. Mount the periphery board (4-loop) (3) with the 13 fixing screws (2) to the
threaded bolts (1) that are embedded in the rear panel or mounting plate
(FC2060).
2. Wire up the periphery board (4-loop) according to the following pin assignment.
3. Re-install any modules that you may have had to remove.
5.4.2 Pin assignments
Inputs and outputs which are not used do not requ
ire termination.
FDnet detector lines which are not used must not be terminated.
5.4.2.1 X1 supply
Pin Designation Description
1 #BATT Message input from the power supply: Battery fault
2 #CONV Message input from the power supply: Converter fault
3 #MAINS Message input from the power supply: Mains failure
4 COMMON Ground
5 3SRC+ Third power supply input (+) [FR]
6 3SRC– Third power supply input (–) [FR]
7 VSYS+ Supply input from the power supply (+)
8 VSYS+ Supply input from the power supply (+)
9 VSYS– Supply input from the power supply (–)
10 VSYS– Supply input from the power supply (–)
Admissible cable cross-section: 0.2…2.5 mm²
3SRC
-
2
1
4
3
X1
6
5
3SRC+
COMMON
#MAINS
#CONV
#BATT
8
7
10
9
VSYS
-
VSYS+
VSYS+
VSYS
-

Table of Contents