Mounting and installation of the compact control panels
Door cont
act kit [DE]
5
245 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
5.36.2 Pin assignments
Inputs and outputs which are not used do not require termination.
5.36.2.1 X6 intrusion detection system / local alarm / identification
lamp
Pin Designation Description
8 Ke Leuchte + Identification lamp (+)
7 Ke Leuchte - Identification lamp (-)
6 Oertl Alarm + Local alarm (+)
5 Oertl Alarm - Local alarm (-)
4 - Not used
3 FSD sabotage, closer (normally open)
2 FSD sabotage, common
1 FSD sabotage, opener (normally open)
Admissible cable cross-section: 0.2…1.5 mm²
1* Horn or beacon
2*
FSD sabotage, connection for "Transmission intrusion detection system"
(can be connected as NO or NC)
3* If necessary
5
6
X6
Oertl Alarm -
Oertl Alarm +
7
8
Ke Leuchte -
Ke Leuchte +
2
3
4
2
1
-
+
-
+
40 ... 2k
ΩΩ
1*
2*
2*
3*
300mA / max. 7.5W
560
2W
Ω
3*