EasyManua.ls Logo

Siemens FS20 - Page 178

Siemens FS20
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and installation of the compact control panels
Module bus cards
5
178 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
Connector Pin Designation Description
X11 1 IO_1 Configurable input/output 1
2 IO_2 Configurable input/output 2
3 IO_3 Configurable input/output 3
4 IO_4 Configurable input/output 4
X12 1 IO_5 Configurable input/output 5
2 IO_6 Configurable input/output 6
3 VSYS_01 Supply output 1 (+)
4 GND_01 Supply output 1 (–)
X11 5 IO_7 Configurable input/output 7
6 IO_8 Configurable input/output 8
7 IO_9 Configurable input/output 9
8 IO_10 Configurable input/output 10
X12 5 IO_11 Configurable input/output 11
6 IO_12 Configurable input/output 12
7 VSYS_02 Supply output 2 (+)
8 GND_02 Supply output 2 (–)
Admissible cable cross-section: 0.2…1.5 mm²
5.19.2.10 Connection terminals for the I/O card (horn/monitored) in
the card cage
The I/O card (horn/monitored) FCI2009-A1 determines the PIN assignment of the
connection terminals for the module bus cards in the card cage.
External connections on the card cage using the example of module bus card 1
with the associated connection terminals X11 and X12:
The external connections of module bus card 2 are on connection terminals
X21 and X22
The external connections of module bus card 3 are on connection terminals
X31 and X32
The external connections of module bus card 4 are on connection terminals
X41 and X42
The external connections of module bus card 5 are on connection terminals
X51 and X52
Depending on the card cage, not all slots may be available for module bus cards
and connection terminals. However, the numbering and assignment of the
connection terminals are identical on all card cages.
43
658
7
2143
6
5
8
7
2
1
X11
X12

Table of Contents

Other manuals for Siemens FS20