Mounting and installation of the compact control panels
5
184 | 354
Switching for relays ↑ RT alarm and RT fault
Figure 98: Switching for relays RT Alarm and RT Fault
1 Remote transmission
FAU_… Configured as RT fault relay output
- ↑ Normal operation (no fault) = contact 2/3 closed
Configured as universal relay output
- Normal operation (no fault) = contact 3/4 closed
AL_… Configured as RT alarm or universal relay output
- Normal operation (no alarms) = contact 2/3 closed
2FAU_NO
AL_NC
X11
AL_COM
AL_NO
X12
FAU_NC
NC
C
NO
NC
C
NO