Mounting and installation of the compact control panels
5
188 | 354
5.20.2.2 X2 on RS485 module
Pin Designation Description
4 RS485_A Line A
3 RS485_B Line B
2 Not connected
1 Not connected
Admissible cable cross-section: 0.2…1.5 mm²
T1 First participant
Tn Last participant
*) Stub lines must not exceed 20 m!
● Consider the polarity A, B!
● Terminate the line after the last participant (Tn) with 120 Ω!
X2
RS485_B
RS485_A
*)
A
B