EasyManua.ls Logo

Siemens FS20 - Page 253

Siemens FS20
354 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mounting and installation of the compact control panels
Ethernet switch FN2008 and safety module FN2009
5
253 |
354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
If cabling is being carried out using multiple PMI & mainboards and the FN2008, a
loop can be created accidentally. Please observe the following information.
NOTICE
Loop with Ethernet cable
Impairment of system function
Pay attention to the Ethernet cable connection if you are connecting more
than one PMI & mainboard.
Never connect a port P1…P4 to a por
t P1…P4.
FT2040 Fire terminal with optional power supply and batteries
FH2001-A1 Empty Eco housing
FDCIO222 I/O module (any I/O module possible)
LINE+
LINE-
FDnet loop connection
IN 1 Control input on separate I/O module (e.g. FDCIO222)
1 Connection for detector contact (F1, F2)
1
R
p
Parallel resistor for I/O module
2
P1…P4 Electric Ethernet connections
L1+, (L2+) Vsys + system supply from fire terminal board
3
M1, (M2) Vsys - system supply from fire terminal board
3
1
The detector contact is normally wired on a free I/O connection of the periphery
board. If all connections are occupied or if using the FT2040 fire terminal, the
detector contact must be connected via an I/O module (e.g. an FDCIO222). In this
instance, the signal of the I/O module must not be configured as 'Degraded alarm
relevant'.
If a station is located very close to the FT2040 fire terminal, the detector contact
can also be wired directly to this station.
2
The parallel resistor for the detector contact depends on the I/O module used.
Refer to the documentation provided with the I/O module used for more details.
3
Use of the redundant L2+/M2 supply inputs is optional and not necessary for EN-
54 compatibility.

Table of Contents

Other manuals for Siemens FS20

Related product manuals