Mounting and installation FC2080
Processor unit (19", FC2080)
6
270 | 354
Building Technologies
008851_s_en_
--
Fire Safety
2016
-
-
27
6.2.3.2 X10 connector terminal for supply
Pin Designation Description
1 #BATT Battery signal monitoring (normally open)
2 COMMON GND for BATT (normally open)
3 #MAINS Signal monitoring power supply system
4 COMMON GND for MAINS
5 3SRC+ 3
rd
source (DC 7…30 V) [FR]
6 3SRC- 3
rd
source (0 V) [FR]
7 VSYS+ System supply (DC 24 V)
8 VSYS+ System supply (DC 24 V)
9 VSYS- System supply (0 V)
10 VSYS- System supply (0 V)
Admissible cable cross-section: 0.5…2.5 mm²
You will find details about signal monitoring and wiring diagrams in the product
data of the power supply (150 W).
See also
2 Installing the power supply kit (150 W, B) [ 282]
6.2.3.3 X41 / X42 / X51 / X52 connection terminals for module bus
cards
The module bus card determines the PIN assignment of the connectors. You will
find the pin assignments in the description of the corresponding module card.
The assignment of the connector is:
Connections of module bus card 4 are on connectors X41 and X42
Connections of module bus card 5 are on connectors X51 and X52
See also
2 Pin assignments [ 167]