Introducing the S7-200 Micro PLC
1-9
S7-200 Programmable Controller System Manual
A5E00066097-02
Table 1-3 Maximum I/O Configurations for S7-200 CPUs
Module 5V ma
Digital
Inputs
Digital
Outputs
Analog
Inputs
Analog
Outputs
CPU 221 No expansion possible
CPU 222
Max Digital In/Out
CPU
2 x EM 223 DI16/DO16 x DC24V
or
2 x EM 223 DI16/DO16 x DC24V/Rly
Total =
+340
-320 or
-300
>0
8
32
40
6
32
38
Max Analog In
CPU
2 x EM 235 AI4/AQ1
Total =
+340
-60
>0
8
8
6
6
8
8
2
2
Max Analog Out
CPU
2 x EM 232 AQ2
Total =
+340
-40
>0
8
8
6
6
0
0
4
4
CPU 224
Max Digital In/Rly Out
CPU
4 x EM 223 DI16/DO16 x DC24V/Rly
2 x EM 221 DI8 x DC24V
Total =
+660
-600
-60
=0
14
64
16
94
10
64
74
Max Digital In/DC Out
CPU
4 x EM 223 DI16/DO16 x DC24V
Total =
+660
-640
>0
14
64
78
10
64
74
Digital In/Max Rly Out
CPU
4 x EM 223 DI16/DO16 x DC24V/Rly
1 x EM 222 DO8 x Rly
Total =
+660
-600
-40
>0
14
64
78
10
64
8
82
CPU 226
Max Digital In/Rly Out
CPU
6 x EM 223 DI16/DO16 x DC24V/Rly
1 x EM 223 DI8/DO8 x DC24V/Rly
Total =
+1000
-900
-80
>0
24
96
8
128
16
96
8
120
Max Digital In/DC Out
CPU
6 x EM 223 DI16/DO16 x DC24V
1 x EM 221 DI8 x DC24V
Total =
+1000
-960
-30
>0
24
96
8
128
16
96
112
CPU 224 or CPU 226
Max Analog In
CPU
7 x EM 235 AI4/AQ1
Total =
>660
-210
>0
14 (24)
14 (24)
10 (16)
10 (16)
28
28
7
7
Max Analog Out
CPU
7 x EM 232 AQ2
Total =
>660
-140
>0
14 (24)
14 (24)
10 (16)
10 (16)
0
0
14
14