EasyManua.ls Logo

Siemens SIMATIC S7-200 - Configuring DIP Switches for the EM 231 Thermocouple Module; Selecting the Thermocouple Type; Selecting Sensor Burnout Direction

Siemens SIMATIC S7-200
606 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
S7-200 Specifications
A-69
S7-200 Programmable Controller System Manual
A5E00066097-02
Configuring the EM 231 Thermocouple Module
The configuration DIP switches are located on the bottom of the module, as shown
in Figure A-35. For the DIP switch settings to take effect, you need to power cycle
the PLC and/or the user 24V
power supply.
DIP switch 4 is reserved for future use. Set DIP switch 4 to the 0 (down) position.
Refer to Table A-22 through Table A-26 for other DIP switch settings.
1 - On
0 - Off
1234*56
DIP ON
Configuration
78
* Set dipswitch 4 to the 0 (down) position.
Figure A-35 Configuring DIP Switches for the EM 231 Thermocouple Module
Selecting the thermocouple type Select the thermocouple type by setting DIP
switches 1, 2, and 3 as shown in Table A-42.
Table A-22 Selecting the Thermocouple Type
Thermocouple Type
SW1 SW2 SW3
J (Default) 0 0 0
K 0 0 1
T 0 1 0
E 0 1 1
R 1 0 0
S 1 0 1
N 1 1 0
+/-80mV 1 1 1
Selecting the sensor burnout direction Select the sensor burnout direction
(either upscale or downscale) by setting DIP switch 5 as shown in Table A-23.
Table A-23 Selecting Sensor Burnout Direction
Burnout Direction
SW5
Upscale (+3276.7 degrees) 0
Downscale (-3276.8 degrees) 1

Table of Contents

Other manuals for Siemens SIMATIC S7-200

Related product manuals