Table 9-20 lists the different types of interrupt events.
Table 9-20 Interrupt Events
Event
Number
Interrupt Description
CPU
221
CPU
222
CPU
224
CPU
226
0 Rising edge, I0.0 Y Y Y Y
1 Falling edge, I0.0 Y Y Y Y
2 Rising edge, I0.1 Y Y Y Y
3 Falling edge, I0.1 Y Y Y Y
4 Rising edge, I0.2 Y Y Y Y
5 Falling edge, I0.2 Y Y Y Y
6 Rising edge, I0.3 Y Y Y Y
7 Falling edge, I0.3 Y Y Y Y
8 Port 0: Receive character Y Y Y Y
9 Port 0: Transmit complete Y Y Y Y
10 Timed interrupt 0, SMB34 Y Y Y Y
11 Timed interrupt 1, SMB35 Y Y Y Y
12 HSC0 CV=PV (current value = preset value) Y Y Y Y
13 HSC1 CV=PV (current value = preset value) Y Y
14 HSC1 direction changed Y Y
15 HSC1 external reset Y Y
16 HSC2 CV=PV (current value = preset value) Y Y
17 HSC2 direction changed Y Y
18 HSC2 external reset Y Y
19 PLS0 pulse count complete interrupt Y Y Y Y
20 PLS1 pulse count complete interrupt Y Y Y Y
21 Timer T32 CT=PT interrupt Y Y Y Y
22 Timer T96 CT=PT interrupt Y Y Y Y
23 Port 0: Receive message complete Y Y Y Y
24 Port 1: Receive message complete Y
25 Port 1: Receive character Y
26 Port 1: Transmit complete Y
27 HSC0 direction changed Y Y Y Y
28 HSC0 external reset Y Y Y Y
29 HSC4 CV=PV (current value = preset value) Y Y Y Y
30 HSC4 direction changed Y Y Y Y
31 HSC4 external reset Y Y Y Y
32 HSC3 CV=PV (current value = preset value) Y Y Y Y
33 HSC5 CV=PV (current value = preset value) Y Y Y Y