S7-200 Specifications
A-76
S7-200 Programmable Controller System Manual
A5E00066097-02
Table A-29 Temperature Ranges (°F) for Thermocouple Types
Data Word
(1 digit = 0.1°F)
T
yp
e J T
yp
e K T
yp
e T T
yp
e E T
yp
e R
,
S T
yp
e N
80 mV
Dec Hex
Type
J
Type
K
Type
T
Type
E
Type
R
,
S
Type
N
80
mV
32767 7FFF >2192.0 F >2502.0 F >752.0 F >1832.0F >3214.0F >2372.0F >94.071mV
OF
32511 7EFF
94.071mV
32140 7D90 3214.0F
94
.
071mV
OR
27649 6C01
80.0029mV
27648 6C00 2764.8F 80mV
: :
25020 61B8 2502.0F
NR
: : overrange
NR
23720 5CA8 2372.0F 2372.0F
:
:
21920 55A0 2192.0F
: :
18320 4790 1832.0F
: :
7520 1D60 752.0F 752.0F
: :
320 0140 underrange 32.0F
: :
1 0001 0.1F 0.1F 0.1F 0.1F 0.1F 0.1F 0.0029mV
0 0000 0.0F 0.0F 0.0F 0.0F 0.0F 0.0F 0.0mV
-1 FFFF -0.1F -0.1F -0.1F -0.1F -0.1F -0.1F -0.0029mV
: :
-580 FDBC -58.0F
: :
-2380 F6B4 -238.0F
: :
-3280 F330 underrange -328.0F underrange
: :
-3460 F27C -346.0F
: : underrange
-4270 EF52 -427.0F -427.0F
: : underrange underrange
-4540 EE44 -454.0F -454.0F -454.0F -454.0F
: :
-27648 9400  -80mV
-27649 93FF -80.0029mV
: :
-32512 8100
-94.071mV
OR
-3268 8000 <-346.0° F <-454.0° F <-454.0° F <-454.0° F <-58.0° F <-454.0° F <-94.07 mV UF
*OF = Overflow; OR = Overrange; NR = Normal range; UR = Underrange; UF = Underflow
indicates that all analog values greater than this and below the open wire threshold report the overflow data value, 32767 (0x7FFF).
indicates that all analog values less than this and greater than the open wire threshold report the underflow data value, -32768 (0x8000).