Table A-35 Temperature Ranges (°C) and Accuracy for RTD Types
System Word (1 digit = 0.1 C)
Pt100
Pt200
Ni100,
Decimal Hex
Pt10000
,
,
Pt500, Pt1000
Ni120,
Ni1000
Cu9.035 0 - 150Ω 0 - 300Ω 0 - 160Ω
32767 7FFF
32766 7FFE ↑ ↑ ↑
32511 7EFF
176.383Ω 352.767Ω 705.534Ω
29649 6C01 150.005Ω 300.011Ω 600.022Ω
27648 6C00 150.000Ω 300.000Ω 600.000Ω
25000 61A8 ↑
18000 4650 OR
15000 3A98
13000 32C8 ↑ ↑
10000 2710 1000.0C 1000.0C
8500 2134 850.0C
6000 1770 600.0C ↑
3120 0C30 ↑ 312.0C
2950 0B86 295.0C
2600 0A28 260.0C
2500 09C4 250.0C
1 0001 0.1 C 0.1C 0.1C 0.1C 0.005Ω 0.011Ω 0.022Ω
0 0000 0.0 C 0.0C 0.0C 0.0C 0.000Ω 0.000Ω 0.000Ω
-1 FFFF -0.1C -0.1 -0.1C -0.1C (negative values are not possible)
NR
↓ ↓↓
-600 FDA8 -60.0C
-1050 FBE6 -105.0C
↓
-2000 F830 -200.0C -200.0 -200.0C
-2400 F6A0 -240.0C
-2430 F682 -243.0C -243.0C ↓
↓ ↓
-5000 EC78
-6000 E890 UR
-10500 D6FC ↓
-12000 D120
-20000 4E20
-32767 8001
-32768 8000
Accuracy over full span 0.4% 0.1% 0.2% 0.5% 0.1% 0.1% 0.1%
Accuracy (nominal range) 4C 1C 0.6C 2.8C 0.15Ω 0.3Ω 0.6Ω
*OF = Overflow; OR = Overrange; NR = Nominal range; UR = Underrange; UF = Underflow