S7-200 Specifications
A-83
S7-200 Programmable Controller System Manual
A5E00066097-02
Table A-35 Temperature Ranges (°C) and Accuracy for RTD Types
System Word (1 digit = 0.1 C)
Pt10000
Pt100
,
Pt200
,
Ni100,
Ni120
C 9 035
0 150
0 300
0 160
Decimal Hex
Pt10000
Pt100
,
Pt200
,
Pt500, Pt1000
,
Ni120,
Ni1000
Cu9.035 0 - 150 0 - 300 0 - 160
32767 7FFF
32766 7FFE
32511 7EFF
176.383 352.767 705.534
29649 6C01 150.005 300.011 600.022
27648 6C00 150.000 300.000 600.000
25000 61A8
18000 4650 OR
15000 3A98
13000 32C8
10000 2710 1000.0C 1000.0C
8500 2134 850.0C
6000 1770 600.0C
3120 0C30 312.0C
2950 0B86 295.0C
2600 0A28 260.0C
2500 09C4 250.0C
1 0001 0.1 C 0.1C 0.1C 0.1C 0.005 0.011 0.022
0 0000 0.0 C 0.0C 0.0C 0.0C 0.000 0.000 0.000
-1 FFFF -0.1C -0.1 -0.1C -0.1C (negative values are not possible)
NR
↓↓
NR
-600 FDA8 -60.0C
-1050 FBE6 -105.0C
-2000 F830 -200.0C -200.0 -200.0C
-2400 F6A0 -240.0C
-2430 F682 -243.0C -243.0C
-5000 EC78
-6000 E890 UR
-10500 D6FC
-12000 D120
-20000 4E20
-32767 8001
-32768 8000
Accuracy over full span 0.4% 0.1% 0.2% 0.5% 0.1% 0.1% 0.1%
Accuracy (nominal range) 4C 1C 0.6C 2.8C 0.15 0.3 0.6
*OF = Overflow; OR = Overrange; NR = Nominal range; UR = Underrange; UF = Underflow
or indicate that all analog values exceeding the limits report the selected burnout value, 32767 (0x7FFF) or -32768 (0x8000).