EasyManua.ls Logo

Siemens SIMATIC S7-200 - S7-200 Troubleshooting Guide

Siemens SIMATIC S7-200
606 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-1
S7-200 Programmable Controller System Manual
A5E00066097-02
S7-200 Troubleshooting Guide
Table D-1 S7-200 Troubleshooting Guide
Problem
Possible Causes Solution
Outputs stop
working.
The device being controlled
has caused an electrical surge
that damaged the output.
User program error
Wiring loose or incorrect
Excessive load
Output forced points
When connecting to an inductive load (such
as a motor or relay), a proper suppression
circuit should be used. Refer to Section 2.4.
Correct user program
Check wiring and correct
Check load against point ratings
Check CPU for forced I/O
CPU SF
(System Fault)
light comes on.
The following list describes the
most common causes:
User programming error
0003 Watchdog error
0011 Indirect addressing
0012 Illegal floating point
value
Electrical noise
0001 through 0009
Component damage
0001 through 0010
Read the fatal error code number and refer to
Section B.1:
For a programming error, check the usage of
the FOR, NEXT, JMP, LBL, and Compare
instructions.
For electrical noise:
Refer to the wiring guidelines in
Section 2.3. It is very important that the
control panel is connected to a good
ground and that high voltage wiring is not
run in parallel with low voltage wiring.
Connect the M terminal on the 24 VDC
Sensor Power Supply to ground.
Power supply
damaged.
Over-voltage on the power lines
coming to the unit.
Connect a line analyzer to the system to check
the magnitude and duration of the over-voltage
spikes. Based on this information, add the proper
type arrestor device to your system.
Refer to the wiring guidelines in Section 2.3 for
information about installing the field wiring.
Electrical noise
problems
Improper grounding
Routing on wiring within the
control cabinet.
Input filters are configured for a
speed that is too fast
Refer to the wiring guidelines in Section 2.3. It is
very important that the control panel is connected
to a good ground and that high voltage wiring is
not run in parallel with low voltage wiring.
Connect the M terminal on the 24 VDC Sensor
Power Supply to ground.
Increase the input filter delay in the system data
block. Refer to Section 5.2.
D

Table of Contents

Other manuals for Siemens SIMATIC S7-200

Related product manuals