S7-200 Specifications
A-8
S7-200 Programmable Controller System Manual
A5E00066097-02
Table A-2 Specifications for CPU 221 DC/DC/DC and CPU 221 AC/DC/Relay (continued)
Description
Order Number
CPU 221 AC/DC/Relay
6ES7 211-0BA21-0XB0
CPU 221 DC/DC/DC
6ES7 211-0AA21-0XBO
Input Features
Number of integrated inputs
Input type
6 inputs
Sink/Source (IEC Type 1 sink)
6 inputs
Sink/Source (IEC Type 1 sink)
Input Voltage
Maximum continuous permissible
Surge
Rated value
Logic 1 signal (minimum)
Logic 0 signal (maximum)
30 VDC
35 VDC for 0.5 s
24 VDC at 4 mA, nominal
15 VDC at 2.5 mA, minimum
5 VDC at 1 mA, maximum
30 VDC
35 VDC for 0.5 s
24 VDC at 4 mA, nominal
15 VDC at 2.5 mA, minimum
5 VDC at 1 mA, maximum
Isolation (Field Side to Logic Circuit)
Optical isolation (galvanic)
Isolation groups of
500 VAC for 1 minute
4 points/2 points
500 VAC for 1 minute
4 points/2 points
Input Delay Times
Filtered Inputs and Interrupt Inputs
0.2 to 12.8 ms, user-selectable 0.2 to 12.8 ms, user-selectable
HSC Clock Input Rate
Single Phase
Logic 1 Level = 15 to 30 VDC
Logic 1 Level = 15 to 26 VDC
Quadrature
Logic 1 Level = 15 to 30 VDC
Logic 1 Level = 15 to 26 VDC
20 kHz
30 kHz
10 kHz
20 kHz
20 kHz
30 kHz
10 kHz
20 kHz
Connection of 2-Wire Proximity Sensor (Bero)
Permissible leakage current
1 mA, maximum 1 mA, maximum
Cable Length
Unshielded (not HSC)
Shielded
HSC inputs, shielded
300 m
500 m
50 m
300 m
500 m
50 m
Number of Inputs ON Simultaneously
40 ° C
55 ° C
6
6
6
6
Output Features
Number of integrated outputs
Output type
4 outputs
Solid State-MOSFET
4 outputs
Relay, dry contact
Output Voltage
Permissible range
Rated value
Logic 1 signal at maximum current
Logic 0 signal with 10 K load
20.4 to 28.8 VDC
24 VDC
20 VDC, minimum
0.1 VDC, maximum
5 to 30 VDC or 5 to 250 VAC
-
-
-
Output Current
Logic 1 signal
Number of output groups
Number of outputs ON (maximum)
Per group - horizontal mounting (maximum)
Per group - vertical mounting (maximum)
Maximum current per common/group
Lamp load
ON state resistance (contact resistance)
Leakage current per point
Surge current
Overload protection
0.75 A
1
4
4
4
3.0 A
5.0 W
0.3
10
µA, maximum
8 A for 100 ms, maximum
No
2.00 A
2
4
3 and 1
3 and 1
6.0 A
30 W DC/200 W AC
0.2 , maximum when new
-
7 A with contacts closed
No