Table 6-38 Internal Analog Output 2 Menu (2855) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2856 1 Internal analog output 2 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2858 0 Internal analog output 2 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2851 % 0 -300 300 Internal analog output 2 minimum
Output Max 2852 % 100 -300 300 Internal analog output 2 maximum
Hardware Zero 2853 0 -200 200 Internal analog input 2 zero
Hardware Span 2854 1 0.75 1.25 Internal Analog Input 2 span
Output Default 2859 % 0 0 100 Analog output 2 watchdog default value
Table 6-39 Internal Analog Output 3 Menu (2645) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2646 1 Internal analog output 3 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2648 0 Internal analog output 3 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2641 % 0 -300 300 Internal analog output 3 minimum
Output Max 2642 % 100 -300 300 Internal analog output 3 maximum
Hardware Zero 2643 0 -200 200 Internal analog input 3 zero
Hardware Span 2644 1 0.75 1.25 Internal Analog Input 3 span
Output Default 2647 % 0 0 100 Analog output 3 watchdog default value
Table 6-40 Internal Analog Output 4 Menu (2653) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2654 1 Internal analog output 4 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2656 0 Internal analog output 4 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2649 % 0 -300 300 Internal analog output 4 minimum
Output Max 2650 % 100 -300 300 Internal analog output 4 maximum
Hardware Zero 2651 0 -200 200 Internal analog input 4 zero
Hardware Span 2652 1 0.75 1.25 Internal Analog Input 4 span
Output Default 2655 % 0 0 100 Analog output 4 watchdog default value
Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
NXGPro+ Control Manual
120 Operating Manual, A5E50491925A