Table 6-41 Internal Analog Output 5 Menu (2661) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2662 1 Internal analog output 5 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2664 0 Internal analog output 5 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2657 % 0 -300 300 Internal analog output 5 minimum
Output Max 2658 % 100 -300 300 Internal analog output 5 maximum
Hardware Zero 2659 0 -200 200 Internal analog input 5 zero
Hardware Span 2660 1 0.75 1.25 Internal Analog Input 5 span
Output Default 2663 % 0 0 100 Analog output 5 watchdog default value
Table 6-42 Internal Analog Output 6 Menu (2669) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2670 1 Internal analog output 6 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2672 0 Internal analog output 6 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2665 % 0 -300 300 Internal analog output 6 minimum
Output Max 2666 % 100 -300 300 Internal analog output 6 maximum
Hardware Zero 2667 0 -200 200 Internal analog input 6 zero
Hardware Span 2668 1 0.75 1.25 Internal Analog Input 6 span
Output Default 2671 % 0 0 100 Analog output 6 watchdog default value
Table 6-43 Internal Analog Output 7 Menu (2677) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2678 1 Internal analog output 7 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2680 0 Internal analog output 7 mode:
• 4 to 20 mA
• 0 to 20 mA
Output Min 2673 % 0 -300 300 Internal analog output 7 minimum
Output Max 2674 % 100 -300 300 Internal analog output 7 maximum
Hardware Zero 2675 0 -200 200 Internal analog input 7 zero
Hardware Span 2676 1 0.75 1.25 Internal Analog Input 7 span
Output Default 2679 % 0 0 100 Analog output 7 watchdog default value
Parameter Assignment/Addressing
6.6 Options for Drive Menu (2) - second part
NXGPro+ Control Manual
Operating Manual, A5E50491925A 121