Table 6-44 Internal Analog Output 8 Menu (2685) Parameters
Parameter ID Unit Default Min Max Description
Analog variable 2686 1 Internal analog output 8 source pick list.
See Pick list for Internal Analog Output Source.
Output Mode 2688 0 Internal analog output 8 mode:
4 to 20 mA
0 to 20 mA
Output Min 2681 % 0 -300 300 Internal analog output 8 minimum
Output Max 2682 % 100 -300 300 Internal analog output 8 maximum
Hardware Zero 2683 0 -200 200 Internal analog input 8 zero
Hardware Span 2684 1 0.75 1.25 Internal Analog Input 8 span
Output Default 2687 % 0 0 100 Analog output 8 watchdog default value
Table 6-45 Pick list for Internal Analog Output Source
Motor Voltage Neg Sequence Q Out Neutral Volts Analog Input #8
Total Current Input Frequency Synch Motor Field Input KVAR
Average Power Input Power Avg Motor Torque Drive Losses
Motor Speed Input Pwr Factor Encoder Speed Excess React Current
Speed Demand Ah Harmonic Analog Input #1 Speed Droop Percent
Speed Reference Bh Harmonic Analog Input #2 Torq Current (Iqs) Ref
Raw Flux Demand Total Harmonics Analog Input #3 Torq Current (Iqs) Fb
Flux Reference Xfmr Therm Level Analog Input #4 Torq Current (IqsFilt) Filtered
Current (RMS) 1 Cycle Protect Analog Input #5
Zero Sequence Av Single Phase Cur Analog Input #6
Neg Sequence D Under Volt Limit Analog Input #7
Table 6-46 Output Connection Menu (2900) Parameters
Parameter ID Unit Default Min Max Description
Filter CT sec
turns
2910 0 0 250 Assuming primary turns = 5, sec‐
ondary side turns of the CTs is used
to measure 󹪝lter capacitor cur‐
rents (not used if Filter Currents
Source is set to "output CTs")..
Filter Currents
Source
2918 Filter CTs Sets the source of 󹪝lter current val‐
ues used in the compensation al‐
gorithm.
Filter induc‐
tance
2920 % 0.0 0.0 20.0 Set the output 󹪝lter inductor, i.e.
impedance value, as a ratio of the
base output impedance of the
drive; typically 5%.*