• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed to be selected if the analog source is one of
the internal I/O inputs.)
Dene the minimum and maximum values for scaling, and the loss of signal (LOS) threshold and
action.
Table 6-63 Analog Input #1 Menu (4100) Parameters
Parameter ID Unit Default Min Max Description
Source 4105 O Set the input source for analog input 1:
• O
• Ext 1 to 24
• Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4110 4–20 mA Set the operational mode for analog input 1:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4120 % 0.0 -300.0 300.0 Minimum analog input.
Max input 4130 % 100.0 -300.0 300.0 Maximum analog input.
Loss point threshold 4140 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4150 Preset Select loss of signal action:
• Preset
• Maintain
• Stop
Loss of signal set‐
point
4160 % 20.0 -200.0 200.0 Loss of signal preset speed.