Table 6-64 Analog Input #2 Menu (4170) Parameters
Parameter ID Unit Default Min Max Description
Source 4175 O Set the input source for analog input 2:
• O
• Ext 1 to 24
• Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4180 4–20 mA Set the operational mode for analog input 2:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4190 % 0.0 -300.0 300.0 Minimum analog input.
Max input 4200 % 100.0 -300.0 300.0 Maximum analog input.
Loss point threshold 4210 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4220 Preset Select loss of signal action:
• Preset
• Maintain
• Stop
Loss of signal set‐
point
4230 % 20.0 -200.0 200.0 Loss of signal preset speed.
Table 6-65 Analog Input #3 Menu (4232) Parameters
Parameter ID Unit Default Min Max Description
Source 4233 O Set the input source for analog input 3:
• O
• Ext 1 to 24
• Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4234 4–20 mA Set the operational mode for analog input 3:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4235 % 0.0 -300.0 300.0 Minimum analog input.
Max input 4236 % 100.0 -300.0 300.0 Maximum analog input.
Loss point threshold 4237 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
NXGPro+ Control Manual
140 Operating Manual, A5E50491925A