Parameter ID Unit Default Min Max Description
Loss of signal action 4238 Preset Select loss of signal action:
Preset
Maintain
Stop
Loss of signal set‐
point
4239 % 20.0 -200.0 200.0 Loss of signal preset speed.
Table 6-66 Analog Input #4 Menu (4332) Parameters
Parameter ID Unit Default Min Max Description
Source 4333 O󹪜 Set the input source for analog input 4:
O󹪜
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4334 4–20 mA Set the operational mode for analog input 4:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4335 % 0.0 -300.0 300.0 Minimum analog input.
Max input 4336 % 100.0 -300.0 300.0 Maximum analog input.
Loss point threshold 4337 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4338 Preset Select loss of signal action:
Preset
Maintain
Stop
Loss of signal set‐
point
4339 % 20.0 -200.0 200.0 Loss of signal preset speed.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
NXGPro+ Control Manual
Operating Manual, A5E50491925A 141