Table 6-67 Analog Input #5 Menu (4341) Parameters
Parameter ID Unit Default Min Max Description
Source 4342 O󹪜 Set the input source for analog input 5:
O󹪜
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Note: Analog input number is redundant since the
menu displays the input number.
Type 4343 4–20 mA Set the operational mode for analog input 5:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4344 % 0.0 -300.0 300.0 Minimum analog input.
Max input 4345 % 100.0 -300.0 300.0 Maximum analog input.
Loss point threshold 4346 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4347 Preset Select loss of signal action:
Preset
Maintain
Stop
Loss of signal set‐
point
4348 % 20.0 -200.0 200.0 Loss of signal preset speed.
Table 6-68 Auxiliary Input #1 Menu (4500) Parameters
Parameter ID Unit Default Min Max Description
Source 4510 O󹪜 Auxiliary input 1 source:
O󹪜
Ext 1 to 24
Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4520 4–20 mA Set the operational mode for auxiliary input 1:
0 to 20 mA
4 to 20 mA
0 to 10 V
-10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4530 % 0.0 -300.0 300.0 Minimum auxiliary input.
Max input 4540 % 100.0 -300.0 300.0 Maximum auxiliary input.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
NXGPro+ Control Manual
142 Operating Manual, A5E50491925A