Parameter ID Unit Default Min Max Description
Loss point threshold 4550 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4560 Preset Select loss of signal action:
• Preset
• Maintain (maintains command)
• Stop
Loss of signal set‐
point
4570 % 20.0 -200.0 200.0 Loss of signal preset speed.
Table 6-69 Auxiliary Input #2 Menu (4580) Parameters
Parameter ID Unit Default Min Max Description
Source 4590 O Auxiliary input 2 source:
• O
• Ext 1 to 24
• Int 1 to 12
See Table Pick list for Analog Input Sources.
Type 4600 4–20 mA Set the operational mode for auxiliary input 2:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input 4610 % 0.0 -300.0 300.0 Minimum auxiliary input.
Max input 4620 % 100.0 -300.0 300.0 Maximum auxiliary input.
Loss point threshold 4630 % 15.0 0.0 100.0 Threshold where loss of signal action is activated.
Enter as percentage of upper range for any type.
Loss of signal action 4640 Preset Select loss of signal action:
• Preset
• Maintain
• Stop
Loss of signal set‐
point
4650 % 20.0 -200.0 200.0 Loss of signal preset speed.
Table 6-70 Pick list for Analog Input Sources
O External 10 External 20 Internal AI6
External 1 External 11 External 21 Internal AI7
External 2 External 12 External 22 Internal AI8
External 3 External 13 External 23 Internal AI9
External 4 External 14 External 24 Internal AI10
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)