Table 6-95 Hour Meter Setup (8010) Parameters
Parameter ID Units Default Min Max Description
Display hour
meter
8020 Function Display the amount of time that the drive has been
operational since it was commissioned.
Preset hour me‐
ter
8030 Function Preset the hour meter to the accumulated time that
the drive has been operational since it was commis‐
sioned in the event that a microboard has been re‐
placed on an existing drive.
Reset hour me‐
ter
8040 Function Reset the hour meter when the drive is commis‐
sioned.
Display Output
kWH meter
8050 Function Display the total output kW hours that have been
accumulated since the drive was commissioned.
Preset output
kWH meter
8060 Function Preset the output kW hour counter to a previous val‐
ue when the microboard is replaced.
Reset output
kWH meter
8070 Function Reset the output kW hour counter to zero.
Display input
kWH meter
8072 Function Display the total input kW hours that have been ac‐
cumulated since the drive was commissioned.
Preset input
kWH meter
8074 Function Preset the input kW hour counter to a previous value
when the microboard is replaced.
Reset input
kWH meter
8076 Function Reset the input kW hour counter to zero.
Table 6-96 Input Harmonics Menu (8140) Parameters
Parameter ID Units Default Min Max Description
Selection for HA 8150 IA Select harmonic analysis:
IA
IB
IC
VA
VB
VC
Harmonics or‐
der
8160 1.0 0.0 30.0 Harmonic order
Harmonics inte‐
gral gain
8170 0.001 0.0 1.0 Harmonics regulator integral gain term
Parameter Assignment/Addressing
6.17 Options for Meter Menu (8)
NXGPro+ Control Manual
Operating Manual, A5E50491925A 165

Table of Contents