Fault Display Type Enable Potential Causes and Corrective Actions
One Pump Not Available A SOP Cause
Drive initiated alarm when the OnePumpFailure_O SOP
󹪞ag is set true and the OnePumpFailureEn_O 󹪞ag is true to
enable it. The default is an alarm and it cannot be changed.
This is used in the Standard SOP for water-cooled drives as an
alarm.
Action
1. Check physical input connected to SOP 󹪞ag.
2. Check for faulty pumps tripped CBs, or obstruction.
Both Pumps Not Available F/A SOP Cause
Drive initiated fault/alarm when the AllPumpsFailure_O
SOP 󹪞ag is set true and the AllPumpsFailureEn_O 󹪞ag is
true to enable it. The default is a fault, but it can be changed
to an alarm by setting the AllPumpsFailureWn_O 󹪞ag
true. This is used in the Standard SOP for water-cooled drives
as a trip alarm.
Action
1. Check physical input connected to SOP 󹪞ag.
2. Check for faulty pumps tripped CBs, or obstruction.
Coolant Cond > 3 uS A SOP Cause
Drive initiated alarm when
the CoolantConductivityAlarm_O SOP 󹪞ag is set true
and the CoolantConductivityAlarmEn_O 󹪞ag is true to
enable it. The default is an alarm and it cannot be changed.
This is used in the Standard SOP for water-cooled drives as an
alarm.
Action
1. Check physical input connected to SOP 󹪞ag.
2. Check conductivity level.
3. Check ionizer.
Coolant Cond > 5 uS F/A SOP Cause
Drive initiated fault/alarm when
the CoolantConductivityAlarm_O SOP 󹪞ag is set true
and the CoolantConductivityAlarmEn_O 󹪞ag is true to
enable it. The default is a fault, but it can be changed to an
alarm by setting the CoolantConductivityAlarmWn_O
󹪞ag true. This is used in the Standard SOP for water-cooled
drives as a trip alarm.
Action
1. Check physical input connected to SOP 󹪞ag.
2. Check conductivity level.
3. Check ionizer.
Troubleshooting Faults and Alarms
11.13 Dedicated I/O for Input Protection
NXGPro+ Control Manual
Operating Manual, A5E50491925A 489