Fault Display Type Enable Potential Causes and Corrective Actions
Coolant Inlet Temp > 60°C F/A SOP Cause
Drive initiated alarm when the InletWaterTempHigh_O
SOP ag is set true and the InletWaterTempHighEn_O
ag is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the InletWaterTempHighWn_O ag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check coolant temperature.
3. Check for ow.
Coolant Inlet Temp < 22°C F/A SOP Cause
Drive initiated alarm when the InletWaterTempLow_O
SOP ag is set true and the InletWaterTempLowEn_O ag
is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the InletWaterTempLowWn_O ag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check coolant temperature.
3. Check for ow.
Cell Water Temp High F/A SOP Cause
Drive initiated alarm when the CellWaterTempHigh_O
SOP ag is set true and the CellWaterTempHighEn_O ag
is true to enable it. The default is an alarm but it can be
changed to a fault by setting
the CellWaterTempHighWn_O ag to False (true is an
alarm). This is used in the Standard SOP for water-cooled
drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check coolant temperature.
3. Check for ow.
Coolant Tank Level < 30 inches A SOP Cause
Drive initiated alarm when the LowWaterLevelAlarm_O
SOP ag is set true and the LowWaterLevelAlarmEn_O
ag is true to enable it. The default is an alarm and it cannot
be changed. This is used in the Standard SOP for water-
cooled drives as an alarm.
Action
1. Check physical input connected to SOP ag.
2. Check sensor.
3. Check and ll tank.
Troubleshooting Faults and Alarms
11.13 Dedicated I/O for Input Protection
NXGPro+ Control Manual
490 Operating Manual, A5E50491925A